UniBus Expansion

Overview

UniBus is a high-speed local expansion bus used to connect expansion boards directly to a Controller or a compatible LAN Module within the same enclosure. It allows for modular growth of I/O, communication ports, and specialized interfaces.

Technical Details

Connectivity

  • Cable: Every UniBus product is supplied with a 270mm UniBus patch cable. Other lengths (150mm to 675mm) are available.
  • Daisy-Chaining: Boards are typically daisy-chained.
  • Maximum Boards:
    • Integriti Access Controller (IAC): Up to 6 boards.
    • Integriti Security Controller (ISC): Check specific model capacity.

Expansion Board Types

  • 2-Door Expander (996535PCB&K): Adds 2 Wiegand ports and 2 Door lock outputs. (Max 3 on IAC).
  • UART Expander (996520PCB&K): Adds 2 UART ports for printers, PC connections, or modems. (Max 4 on IAC).
  • 8 Relay Expander (996515PCB&K): Adds 8 relays. (Max 2 on IAC).
  • 8-Zone Expander (996500): Adds 8 zone inputs. (Note: Not supported on IAC).
  • Lift Interface (996540PCB&K): Adds 16 floors. (Max 6 on IAC).
  • 4 I/P Analogue Expander: Adds 4 analogue inputs.

Configuration / Programming

  • Hot-Plugging: UniBus boards can be connected while the Control Module is powered up. The “Unsecured” System Input will trigger to indicate a new board is present.
  • Relay Mapping (IAC):
    • X01-X16: General purpose outputs.
    • X17-X32: Mimic IAC Door Lock and DOTL outputs.

Troubleshooting

  • UniBus LED:
    • FLASHing: Idle (no boards or cable fault).
    • OFF: OK (communicating correctly).
    • ON: Fault (address conflict or board issue).
  • Power Issues: If a UniBus board is not working, ensure the host module is powered via the 10-way PSU bus or an External PSU Bypass Link (996793) is fitted.