Overview
This guide explains how to integrate the SmartIntego wireless lock system (by Simons Voss) with the Integriti access control platform. SmartIntego uses short-distance wireless communication to link Integriti door modules with Intego-enabled mechanical locks via RS485 Gateway Nodes.
The system supports up to 8 Intego locks and up to 8 Gateway Nodes per door module IAC or ILAM, in any combination. The SLAM supports up to 2 SmartIntego locks. The ISC does not directly interface with SmartIntego — use an ILAM or SLAM with the ISC.
Prerequisites
- Integriti controller with an IAC, ILAM, or SLAM door module.
- SmartIntego Gateway Nodes (model SI.GN.*) and Intego locks.
- SmartIntego Configuration Gateway Node (model SI.GN.CONFIG.UC) with USB and RS485 interfaces.
- SmartIntego software running on a Windows PC for pairing.
- Intego USB Card Programmer connected to the Windows PC.
- SIFER-CA cards (ordered from Inner Range) for sites using both SIFER readers and Intego locks.
- 4-wire RS485 connection (A, B, +12V, GND) from the door module to each Gateway Node.
Step-by-Step
Step 1: Pair Locks and Gateway Nodes (SmartIntego Software)
- Connect the Configuration Gateway Node to the Windows PC via USB.
- Connect the Intego USB Card Programmer to the PC.
- Run the SmartIntego software.
- Pair each Intego lock with its assigned Gateway Node.
- A Gateway Node may have multiple locks paired to it.
- Intego communicates at 868 MHz (Europe) or 920 MHz (AU/NZ).
- Note the Device Address of each lock and the Gateway Node ID — these are needed for Integriti configuration.
- Valid Gateway Node addresses for IAC/ILAM: 2–9.
- Valid Gateway Node addresses for SLAM: 2–3.
- Disconnect the Configuration Gateway Node before connecting the production Gateway Nodes to the door module.
Step 2: Wire the Gateway Node to the Door Module
- Connect 4 wires from the door module’s RS485 reader port to the Gateway Node:
- A — RS485 Data A
- B — RS485 Data B
- +12V — 12 VDC power
- GND — Ground
- Refer to the SmartIntego Gateway Node wiring diagram and Integriti RS485 reader port pinout for correct connections.
Step 3: Configure the Reader in Integriti
- Open the door module configuration in Integriti System Designer.
- Navigate to the Readers section.
- For each Intego lock, configure:
- Reader Type: Set to “Intego”
- Device Address: Set to the Device Address from the SmartIntego software.
- Location: Set the appropriate door location (e.g., “Outside Door 4”).
- Card Format: Set as required for the installation.
- Save the Reader settings.
Step 4: Configure Door Access Control
- Still within the door module configuration, expand Door Access Control.
- For each door/lock pair:
- Select the Hardware Type and Lock Number matching the Intego lock number.
- Click the ellipsis (
...) next to the Door name field to create or select a Door:- Name: Enter a descriptive door name.
- Module: Select the module type and number via the ellipsis.
- Relay: Select
Lock X Intego #X(auto-generated by the software). - Reader: Select
RX Intego ........ (Gateway X)(auto-generated by the software). - Set additional options: Door Type, Locations, Areas, unlock times, Free Access behaviour.
- Save the Door settings.
- Double-click the newly created Door to add it to the door module configuration.
- Save the door module settings.
Step 5: Configure Advanced Options
- Configure any additional settings:
- Free Access (Office Mode): Lock/unlock the Door entity to enable/disable free access. Door actions take approximately 4–8 seconds.
- Zone Inputs: Monitor
Rdr X Faultinput for Battery Low events.
Verification
- Present a SIFER-CA credential at the Intego lock — verify access is granted and the lock engages.
- Check that the credential data reaches the Integriti host via the Gateway Node.
- Verify review events are generated in Integriti for lock activity.
- Test Free Access (Office Mode) — lock and unlock the door from Integriti.
- Monitor the
Rdr X Faultinput for battery level indications.
System Operation
- The Integriti host evaluates all card read data and sends lock/unlock commands to the Gateway Node.
- Lock configuration is sent to the Gateway Node at initial communication and on programming changes.
- When the wireless system is offline from the host, the lock uses a pre-configured whitelist (up to 250 cards) stored in the locking device. Whitelisted cards trigger a brief 5-second unlock.
Limitations
- Maximum 8 Gateway Nodes per IAC/ILAM; 2 per SLAM.
- Maximum 8 locks total per door module (any combination across Gateway Nodes).
- SmartIntego Ethernet model not supported.
- Whitelist limited to 250 cards.
- Door monitoring sensors (fastening screw, deadbolt contact, internal handle) may require additional components — not fully tested with Integriti at time of writing.
- Wireless locks require battery monitoring to ensure operation and performance.
Troubleshooting
| Problem | Resolution |
|---|---|
| Lock not responding | Verify the Gateway Node has power (+12V) and correct RS485 wiring (A/B polarity). Check the Gateway Node is within ~30m of the lock. |
| Card not recognised | Ensure SIFER-CA cards are being used. Verify the Card Format configuration matches. |
| Gateway Node not discovered | Check Gateway Node address is within valid range (2–9 for IAC/ILAM, 2–3 for SLAM). Verify RS485 connection to door module. |
| Offline lock behaviour incorrect | Verify the whitelist has been configured in SmartIntego software. |