Honeywell Fire Panel Interface Cable

Overview

The Honeywell Fire Panel Interface Cable (Part 996239) is a specialized serial data cable used to connect an Inner Range Integriti RS232 UniBus UART Port to the Printer output port on a Honeywell BC-200 Fire Panel. This connection is mandatory for the Integriti-Honeywell Fire Panel integration.

Technical Details

Components and Parts

To construct a custom cable, the following parts are required:

  • Inner Range Modem Cable (P/N 993027).
  • Shielded Data Cable: Minimum 2 conductors @ 7/0.2. Must include a foil shield and 7/0.2 drain wire.
  • Maximum Length: 145 metres.
  • Connectors: 9-Way Male D connector with matching shell and strain relief.

Short Distance Alternative (Up to 5m)

For installations where the distance is less than 5 metres, a pre-assembled solution can be used:

  1. Inner Range Modem Interface Cable (P/N 993027).
  2. DB25 Female to DB9 Male Adapter (e.g., Videk 1058).
  3. DB9 Null Modem Cable (Male-Female) (e.g., MCM NM9-6MF).

Terminal Pinouts

UART to Fire Panel Mapping

10-way UART Header (Socket)Wire Colour9-way Male D Connector (Pin)Signal
Pin 3BlackPin 3Tx / Rx
Pin 4YellowPin 4RTS / CTS
Pin 9ShieldPin 5Shield (Gnd)

Configuration / Programming

Firmware Requirements

The integration requires the following minimum firmware versions:

  • Integriti Controller: V18.1.6 or later.
  • UniBus UART: V1.0.3 or later.

Custom Assembly / Wiring

Assembly should only be performed by a competent technician. The process involves modifying the 25-way D connector end of the 993027 cable:

  1. Remove the shell and de-solder wires from the 25-way D connector.
  2. Extend the conductors and drain wire using the shielded data cable.
  3. Solder to the 9-way Male D connector according to the pinout below.
10-way UART Header (Socket)Wire Colour9-way Male D Connector (Pin)Signal
Pin 3BlackPin 3Tx / Rx
Pin 4YellowPin 4RTS / CTS
Pin 9ShieldPin 5Shield (Gnd)

IMPORTANT

The shield wire must have insulation sleeving fitted to prevent shorts.